Newcastle University School of Chemical Engineering and Advanced Materials
OVERVIEW OF MEASUREMENT SYSTEMS AND DEVICES
(Adapted from a free Online Mini-Course from the ISA Training Institute)
 
CONTENTS
INTRODUCTION
OBJECTIVES
1 Measurement Devices
  1.1 Sensor, transmitter, and transducer review
2 Primary Measuring Element Selection and Characteristics
  2.1 Range
  2.2 Response Time
  2.3 Accuracy vs. Precision
  2.4 Sensor sensitivity
  2.5 Dead band and dead time
  2.6 Cost
  2.7 Installation problems
3 Signal Transmission
  3.1 Signal Types
  3.2 Standard Signal Ranges
  3.3 Electronic Transmitter Adjusted Range
  3.4 Pneumatic Transmitter Adjusted Range
4 Transmission System Dynamics
  4.1 Transmission lag
  4.2 Transmitter gain
  4.3 Smart transmitters
  4.4 Smart transmitter microprocessor-based features
   
   
   
   
   
   
5 Glossary of terms
6

Quiz
Cross-word Puzzle

2. Primary Measuring Element Selection and Characteristics

When selecting the sensor, there are a number of factors to keep in mind. Knowing these factors in advance, and the needs of the process, saves a buyer time and money. Before any of these factors can be considered, the intended use of the sensor must be known. Once that is established, several factors should be considered:

  • Range: What is the normal range over which the controlled variable might vary? Are there extremes to this?
  • Response time: The amount of time required for a sensor to completely respond to a change in its input.
  • Accuracy: How close the sensor comes to indicating the actual value of the measured variable?
  • Precision: How consistent the sensor is in measuring the same value under the same operating conditions over a period of time?
  • Sensitivity: How small a change in the controlled variable the sensor can measure?
  • Dead band: How much of a change to the process is required before the sensor responds to the change?
  • Costs: What are the costs involved - not simply the purchase cost, but also the installed/operating costs?
  • Installation problems: Are there special installation problems, e.g., corrosive fluids, explosive mixtures, size and shape constraints, remote transmission questions, etc.?
2.1 Range

Range is the region in which the controlled variable might vary, in both normal and extreme situations? For instance, if a process normally has a pressure of between 200 and 300 pounds per square inch, a sensor that measures from 100 to 400 pounds would be desirable; this allows for extreme conditions to be measured as well as normal ones. A broad range also allows the operator time to respond when measurements occur outside the norm. Ideally, a process should be 40 to 60, or 30 to 70 percent of the range most of the time and under normal operating conditions.

2.2 Response time

Response time is the amount of time required for a sensor to respond completely to a change in input. The response time of the control loop is the combination of the responses of all the parts, including the sensor. An important objective of control system design is to match correctly the time responses of the control system (and its measurement systems) to that of the process. In general, a system with a quicker response time will be more expensive.


Sensor Response Time (Time Constant)

This figure shows a key principle of sensor response time. It illustrates that in a fixed amount of time, known as the "time constant," here shown as 3 seconds, the sensor registers 63.2% of the total change. In the next time constant, the sensor registers 63.2% of the remaining difference, and so on. In each time constant, the sensor registers the same percent of the remaining difference.

2.3 Accuracy vs. Precision


Precision and Accuracy

These figures contrast the term "precision" as shown above, with the term "accuracy" below. The actual value (70) is shown as a solid line in both figures. The measured values are shown as dots. Accuracy is a measure of how close the sensor comes to indicating the actual value of the measured variable. Here we see that the measured values are scattered above, below and on the actual value. Accuracy is always given in terms of inaccuracy such as +/- 2% or +1%, -3%. Precision is a measure of the consistency of a sensor is in measuring the same value under the same operating conditions over a period of time. The figure shows precise measured values, all the same distance below the actual value. Precision is synonymous with repeatability and may be specified as a range or value excursions or as a percent.

2.3.1 Accuracy

Most devices are rated on their accuracy, not their precision. The specifications usually state that the device is accurate to plus or minus some value. Thus, with accuracy, the deviation is known, but not the direction of the deviation. For example, if a watch has an accuracy of ten minutes, it means an accuracy of plus or minus ten minutes. The owner of this watch has an appointment for 2:30 p.m., but must arrive at 2:20 in order to be on time because of the rated accuracy of the watch. The owner cannot know if the watch is showing the time ten minutes early or ten minutes late or somewhere in between.

2.3.2 Precision

Precision is always within a given value and is always in the same direction. Thus, a precise measurement may be wrong, but it is consistent. For example, another watch has a precision of plus five minutes. The owner of this watch knows that she can arrive at her 2:30 p.m. appointment at 2:35 (on the watch) and still be on time.

2.4 Sensor sensitivity

The sensitivity of the sensor is a measurement of how small a change in the controlled variable it can actually measure. The greater the sensitivity, the greater the sensor's reaction to an input stimulus.

2.5 Dead band and dead time

Dead band is the "unresponsiveness" of the sensor. It describes how much change to the process is required before the sensor actually responds to it or even detects it. The term sensitivity has frequently been used to denote dead band, but the terms are not truly interchangeable. Sensitivity refers to the reaction of the sensor. Dead time applies to the time it takes for the sensor to react.

2.6 Cost

In addition to the above factors, cost must also be considered. Not only the cost of the initial purchase, but also the cost of maintaining the instrument. Very often more money is spent maintaining an instrument than buying it initially.

2.7 Installation problems

Installation problems can include special problems in the environment such as humidity, vibration, temperature, or dust. Installation problems can also be anything that causes a problem to the devices installed, such as, installing the device in a difficult to reach location.

go to first page
First
go to previous page
Previous
go to next page
Next
go to last page
Last


Back to the Swot Shop

© Copyright M.T. Tham (1996-2009)
Please email errors, comments or suggestions to ming.tham@ncl.ac.uk.